Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance. Suitable for fixed installation in dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. Additionally valid also DIN VDE 0298 part 1 and 2. For the installation in conduit all precautions must be taken that no accumulation of water can occur in the pipes.
The cables are halogen-free, have low smoke gas development, no fire propagation and insulation retention in the event of fire for 180 minutes in accordance with VDE 0472 part 814. In addition, the cable has been tested for functional integrity in accordance with DIN 4102 Part 12 (E 90) for all standard carrying systems (Cable troughs and ladders, ceiling installation) and is therefore suitable for use in fire alarm systems, systems for alarming and issuing instructions to people, safety lighting and other backup lighting in accordance with VDE 0108.
The cables are halogen-free, have low smoke gas development, no fire propagation and insulation retention in the event of fire for 180 minutes in accordance with VDE 0472 part 814. In addition, the cable has been tested for functional integrity in accordance with DIN 4102 Part 12 (E 90) for all standard carrying systems (Cable troughs and ladders, ceiling installation) and is therefore suitable for use in fire alarm systems, systems for alarming and issuing instructions to people, safety lighting and other backup lighting in accordance with VDE 0108.
Nominal voltage | Uo/U: 600/1000 V |
Test voltage | 4000 V |
Bending radius fixed (xD) | 12 |
Operating temperature fixed | -30°C bis 90°C |
Operating temperature mobile | -15°C bis 70°C |
Short-circuit temperature | 250°C |
Short circuit duration | 5 sek. |
Standard | security cable in the case of fire to DIN VDE 0266 & FE 180: Insulation integrity to DIN VDE 0472 part 814 & E 30: Function- ality to DIN 4102 part 12 |
Standard CE | CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU. |
inner Conductor | bare copper conductor to DIN VDE 0295 cl. 1 or cl. 2, HD 383 |
core Insultation | special cross-linked halogen-free fire resistant silicone compound |
Core colour code | to DIN VDE 0293-308 |
layer | cores stranded in layers |
Outer sheath material | thermoplastic halogen- free compound type HM4 |