Everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance. Suitable for fixed installation in dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. Additionally valid also DIN VDE 0298 part 1 and 2. For the installation in conduit all precautions must be taken that no accumulation of water can occur in the pipes.
The cables are halogen-free, have low smoke gas development, no fire propagation and insulation retention in the event of fire for 180 minutes in accordance with VDE 0472 part 814. In addition, the cable has been tested for functional integrity in accordance with DIN 4102 Part 12 (E 90) for all standard carrying systems (Cable troughs and ladders, ceiling installation) and is therefore suitable for use in fire alarm systems, systems for alarming and issuing instructions to people, safety lighting and other backup lighting in accordance with VDE 0108.
The cables are halogen-free, have low smoke gas development, no fire propagation and insulation retention in the event of fire for 180 minutes in accordance with VDE 0472 part 814. In addition, the cable has been tested for functional integrity in accordance with DIN 4102 Part 12 (E 90) for all standard carrying systems (Cable troughs and ladders, ceiling installation) and is therefore suitable for use in fire alarm systems, systems for alarming and issuing instructions to people, safety lighting and other backup lighting in accordance with VDE 0108.
Test voltage | 500 V |
Operating temperature fixed | -30°C bis 70°C |
Operating temperature mobile | -5°C bis 50°C |
Standard | adapted to DIN VDE 0815 & FE 180: Insulation integrity to DIN VDE 0472 part 814 IEC 60331 & E 30-E90: Functionality to DIN 4102 part 12. |
Standard CE | CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU. |
inner Conductor | bare copper conductor, solid 0,8 mm |
core Insultation | halogen-free, polymer HI 1 |
Core colour code | acc. to DIN VDE 0815 |
layer | cores twisted to pairs, 4 pairs consistbr>to unit, several units stranded to layersbr>units identified by numbered tapebr>core wrapping with special polyesterbr>and glass-fibre tape |
Overall shielding | plastic coated alu-foil with drain wire |
Outer sheath material | halogen-free, flame retardant to DIN VDE 0207 part 24 HM2 |
JB-H(St)H E30-E90