These insulated wires are suitable for laying in tubes, under and surface mounting of plasters and also in closed installation conduits. These are not allowed to install for direct laying on cable trays, channels or tanks. These types are permitted for the inner wiring of equipment, distributor and switchboards and also for protective laying to the lightings with a nominal voltage up to 1000 V alternating current or up to 750 V direct current against earth.
The materials used are free from silicon and cadmium and free from varnish damaging sustances.
The materials used are free from silicon and cadmium and free from varnish damaging sustances.
Nominal voltage | Uo/U: 450/750 V |
Test voltage | 2500 V |
Bending radius fixed (xD) | 4 |
Operating temperature fixed | -30°C bis 70°C |
Operating temperature mobile | 5°C bis 70°C |
Short-circuit temperature | 160°C |
Fire classes | Eca |
Standard | acc. to DIN VDE 0281 part 3, HD 21.3 S3 and IEC 60227-3, self-extinguishing and flame retardant acc. to VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1, DIN EN 50575 VDE 0482-575:2017-02 |
Standard CE | CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU. |
inner Conductor | bare copper conductor fine-stranded acc. DIN VDE 0295 cl. 5 / IEC 60228 cl. 5 |
core Insultation | Polyvinyl chloride (PVC) |