Halogen-free single-core wires are used for installation in dry enviroments for wiring up lighting fixtures and units where valuable assets are to protected from further damage resulting from fire. These cables may be installed on, in and beneath plaster, as well as in closed installation ducts.
Suitable for fixed lay, in pipe, cable-carrier channels, inner wiring of electric switchboards, inside interruption and control equipments for voltage until
1000V in c.a. and 750V d.c. to the ground.
Suitable for fixed lay, in pipe, cable-carrier channels, inner wiring of electric switchboards, inside interruption and control equipments for voltage until
1000V in c.a. and 750V d.c. to the ground.
Nominal voltage | Uo/U: 450/750 V |
Test voltage | 2500 V |
Bending radius fixed (xD) | 4 |
Operating temperature fixed | -25°C bis 90°C |
Operating temperature mobile | 5°C bis 90°C |
Short-circuit temperature | 250°C |
Short circuit duration | 5 sek. |
Fire classes | Eca |
Standard | DIN EN 50525-3-41; VDE 0285-525-3-41:2012-01, DIN EN 60754-1 VDE 0482-754-1:2021-02, EN 60684-2, DIN EN 61034-2 |
Standard CE | CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU. |
inner Conductor | fine-stranded bare copper acc. DIN VDE 0295 cl. 5 / IEC 60228 cl. 5 |
core Insultation | cross-linked polyolefin, compound typ EI5 to DIN VDE 0282 part 1 |