Power cables for energy supply are installed in open air, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected.

The materials used are free from silicon and cadmium and free from varnish damaging sustances.
Nominal voltage Uo/U: 600/1000 V
Nominal Voltage DC Uo/U: 900/1800 V
Test voltage 4000 V
Bending radius fixed (xD) 15
Operating temperature fixed -5°C bis 70°C
Operating temperature mobile -5°C bis 70°C
Short-circuit temperature 160°C
Short circuit duration 5 sek.
Fire classes Eca
Standard ÖVE K 23 and K 603
Standard CE CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU
inner Conductor bare copper conductor solid or stranded, to DIN VDE 0295 cl. 1 or cl. 2 and IEC 60228 cl. 1 or cl. 2
core Insultation Polyvinyl chloride (PVC)
Core colour code HD 308 S2, (7 cores black with continuous white numbers printed)
layer multi cores stranded in layers
Outer sheath material Polyvinyl chloride (PVC)
Constant Against UV-radiation
E-YY-O
Art.Nr

Net amount
Metal surcharge
Total amount