Halogen-free power cables with enhanced characteristics in case of fire are used for applications where harm to human life and damage to property must be prevented in the event of fire, e.g. in industrial installations, communal establishments, hotels, airports, underground stations, railway stations, hospitals department stores, banks, schools theaters, multi-storey buildings, process control centres etc. Suitable for fixed installation in dry, damp or wet environments, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. The concentric conductor can be used as PE- PEN conductor or as screen.
Nominal voltage | Uo/U: 600/1000 V |
Test voltage | 4000 V |
Operating temperature fixed | -20°C bis 90°C |
Operating temperature mobile | -5°C bis 50°C |
Short-circuit temperature | 250°C |
Short circuit duration | 5 sek. |
Fire classes | auf Anfrage |
Standard | DIN VDE 0276-604:2008-02, DIN EN 50575 VDE 0482-575:2017-02, HD 604 S1 |
Standard CE | CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU. |
inner Conductor | bare copper conductor to DIN VDE 0295 cl. 1 or cl. 2, HD 383 |
core Insultation | halogen-free, cross-linked polyethyle- ne compound 2XI1, to HD 604 S1 |
Core colour code | acc. to DIN VDE 0293-308 and HD 186 |
layer | cores stranded in layers (for multi-corebr>cables) |
Shielding | concentric conductor of plain Cu wires |
inner Sheath Material | overall filled inner sheath, covered by filling compound or wrapped tape |
Overall shielding | konzentrischer Leiter aus blanken Cu-Drähten mit Kupferbandumwicklung |
Outer sheath material | halogen-free polymer HM4 |
N2XCH